TempSense - Technical Details

     
Display 2 Line Alphanumeric LCD with Back light.
Temperature Displayed in Celsius or Fahrenheit
Parameters Temperature values and status
Maximum value recorded per channel
Controller settings
   
Measurement 3 or 4 Contactless Infrared Thermal Sensors
Accuracy +/- 0.1 Degree Celsius
   
Alarm Communication Alarm,
Temperature Exceeded Alarm
Temperature Threshold User Programmable, 25 - 80 Degree Celsius
Alarm Output Relay
DPDT, Rated 3A, 230VAC, Surge Resistance 1500V
   
Event Logging 10 Slots for logging of Alarm Events.
Includes TimeStamp
Non-volatile memory
   
Auxiliary Input 240VAC, 50Hz
   
Enclosure
Controller Front Panel IP50, Rear Panel IP30, Polycarbonate
96 x 96 x 98 mm
Slave IP30, ABS
79 x 33 x 27 mm
 
General
Ambient Temperature 0-65 Degree Celsius
Humidity 0-95%
   
Standards
EN61326 Electrical equipment for measurement, control and laboratory use. EMC requirements
EN61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use. General requirements
EN50081-2 Generic emissions standard for domestic, commercial and light industrial environments. Used when no product specific standards exist.
EN50082-2 Generic emissions standard for domestic, commercial and light industrial environments. Used when no product specific.
   