| General |
|
Network type
(Programmable) |
Single Phase, 3 phase 3 wires, 3 phase 4 wires |
| Accuracy & standard |
According to IEC 1036 Class 1 |
| Ambient temperature |
0-50 deg C |
| Humidity |
0-95% non condensing |
| Input |
|
| Input voltage |
0-500VAC |
| Input voltage tolerance |
80-110% of Un |
| Burden |
< 0.2VA per phase |
| Overload conditions |
4 x In continuous |
| Frequency |
50/60Hz |
| Auxiliary Supply |
230VAC |
| Output (Optional) |
|
| KWh pulse output |
Mercury wetted volt free relay |
| Pulse rate |
1 pulse per kWh or 10kWh |
| Pulse duration |
150 msec |
| Enclosure |
|
| Display |
16 digit LCD, display including 2 decimal places, re-settable |
| Dimension |
DIN 96x96x98mm |
| Panel Mount |
via 4 corner bracket and thumb tensioning screws |
| Panel Cutout |
92 + 0.8mm x 92 + 0.8mm |
| Material |
black polycarbonate complying with UL 94VO. The cover/window is
made from plexiglass 7N |
| Fixing |
Snap on DIN rail 35 x 7.5mm complying with DIN 50022
BS5584 |
| Enclosure code |
Case IP50 / terminal IP 30 complying with IEC529 BS5490 DIN 40050 |
| Terminal |
3.5mm |
| Insulation |
|
| Test voltage |
4kV RMS 50Hz for 1 min |
| Impulse test |
EMC 5kV transient comply with IEC801 / EN55020 |
| HF interference test |
EHF 2.5kV 1MHz comply with IEC255-4 |
| |
|