| Supply voltage Un |
115 V AC (Part number R-ELRM-30V-F)
230V AC (Part number R-ERM-30V-M/
R-ELRM-10V) (85 - 115% of Un) |
| Frequency range |
50/60Hz (AC supplies) |
| Isolation |
Over-voltage category III |
| Rated impulse withstand voltage |
2.5kV (115V AC supply)
4kV (230V AC supply) for 1.2 / 50micro sec IEC60664 |
| Power consumption (max) |
6VA |
| |
|
| Monitored leakage current |
For R-ELRM-30V-* = 0.30A (50/60Hz)
For R-ELRM-10V = 0-10A (50-60Hz) |
| Sensitivity |
For R-ELRM-30V-*
6, 10, 30, 50, 75, 100, 300, 500, 750mA
1, 3, 5, 7.5, 10, 15, 20, 25, 30A (user-selectable)
For R-ELRM-10V
30, 50, 75, 100, 300, 500, 750mA
1, 3, 5, 7.5, 10A (user-selectable) |
| Time delay |
For R-ELRM-30V-*
instantaneous, 50, 250, 500msec,
1, 2.5, 5, 10 sec (user-selectable)
For E-ELRM-10V
instantaneous, 50, 250, 500msec (user-selectable)
Note: for sensitivity setting: of 30mA, the time delay is fixed to
instantaneous, <40msec and is not adjustable |
| Trip level limits |
70 - 80% of sensitivity |
| Reset value |
<7% of tripped level |
| Measured current |
0.005 to <30A displayed on auto ranging 2 digit 7 segment red
LED display |
| Resolution |
100 microA min to 1A max |
| Display accuracy |
+/-15% of actual measured leakage current |
| Reset time |
<120msec (from supply interruption) |
| |
|
| Self test duration |
5 secs. (operates on power on only) |
| Memory |
storage of the leakage fault and reset with "test/reset"
button |
| |
|
| Toroid connection(11,13) |
to external R-ZCT toroid only (1000:1) |
| Toroid withstands capacity |
50kA for 200mS |
| Distance between toroid & relay |
50 metres (max) |
| |
|
| Ambient temperature |
-5 to +60 deg C / -5 to +40 deg C
(in occordance to IEC755) |
| Relative humidity |
+95% |
| |
|
| Output(4, 6, 8, 10, 12, 14) |
2 x SPDT relay |
| Output rating |
| AC1 |
250V 8A (2000VA) |
| AC15 |
250V 2.5A |
| DC1 |
25V 8A (200W) |
|
| Electrical Life |
>= 150,000 operations at rated load |
| Dielectric voltage |
2kV AC(rms) IEC 60947-1 |
| Rated impulse withstand voltage |
4kV (1.2/50 microsec) IEC 60664 |
| Remote "test" / "reset" (5, 7, 9) |
requires two NO contact (ie pushbutton) |
| Minimum trigger time |
>50msec |
| Fault level output(1,2) |
50% at sensitivity setting (factory set)
User adjustable from 10-65% in 5% increments |
| Load |
40mA max @ 240VAC |
| |
|
| Housing |
Grey flame retardant Lexan UL94VO |
| Weight |
approximately 250g |
| Mounting option |
on to 35mm symmetric DIN rail to BS5584:1978
(EN50002, DIN46277-3) |
| Terminal conductor size |
<=2.5mm sq. stranded
<= 4mm sq. solid |
| |
|
| Approvals |
Conforms to IEC755, 50081-1,
50081-2, 50082-1, 50082-2, CE |
| |
|